13
Cable Power Supplies
> Proven CableUPS® uninterruptible power supply
> Programmable LCD Smart Display
> 6, 15 and 22A models available
> Modular design with hot-swappable inverter
> Programmable, temperature-compensated battery charger
> Integrated and External DOCSIS® Transponders
> Integrated and External Proprietary Transponders
XM2
CableUPS
®
Power Supply
XM2
XM2
Models: XM2-910 XM2-915 XM2-915 HV XM2-1350-48 XM2-922 XM2-922 HV
Electrical
Input Voltage (Vac): 120 / 240 120 / 240 120 / 240 120 / 240 200 / 240 200 / 240
Input Voltage Tolerance: ±15% ±15% -25% to +15% ±15% ±15% -25% to +15%
Input Frequency: 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
Frequency Tolerance: ±3% ±3% ±3% ±3% ±3% ±3%
Output Voltage (Vac): 63 / 75 / 87 63 / 75 / 87 63 / 75 / 89 63 / 75 / 87 63 / 75 / 87 63 / 75 / 89
Output Current (A): 10 22.5 / 18 / 15 22.5 / 18 / 15 22.5 / 18 / 15 22.5 22.2
Max Output Power (VA): 900 1350 1350 1350 2025 2025
Waveform: Quasi-square wave
Voltage Regulation: ±5%
Output Frequency Stability: ±0.05% inverter mode, ±1% normal mode
Short Circuit Current: 150% of maximum current rating
Transformer Efficiency: 90% typical line mode, 84% typical standby mode
Transfer Characteristics: Uninterrupted output
Battery Voltage (Vdc): 36 36 36 48 48 48
Battery Charger
Temperature Compensation: Programmable (0 to 5mV/Cell/°C)
Charger Current: 10A at 80% load and nominal input (bulk charge mode)
Three Stage: Bulk, accept, float
Mechanical
Status Display: Smart Display 2 x 20 LCD with backlight
Dimensions
H x W x D (in/mm):
8.8 x 15 x 13 / 222 x 381 x 330
Approx. Weight (lb/kg): 62 / 28 70 / 32 64 / 29 70 / 32 92 / 42 92 / 42
Finish: Black, epoxy powdercoat
Environment
Operating Temperature: -40 to 55°C / -40 to 131°F
Humidity: 0 to 95% non-condensing
Agency Compliance: FCC Part 15 Class A, UL1778, CSA 22.2 No. 107.1-M95
Smart Display Features:
Output current, Input frequency, Battery voltage, Battery temperature, Output VA, Standby time,
Built-in diagnostics, Output power (W), Output voltage, % load, Input voltage, Charger current
Note: General Specifications reference most commonly used models. For model-specific information, consult product manual. Other voltages and configurations may be available. For more information,
contact your sales representative.
Optional Features
PIM/N+1 Protective Interface Module: Provides two programmable outputs from a single XM Series 2 power supply. The PIM protects system components and provides
isolation between distribution legs by shutting down the individual load during over-current conditions. The PIM has a user-programmable over-current threshold, as well as a
programmable over-current tolerance period to specify the time in seconds (1 to 10) that an over-current condition is allowed on the XM Series 2 output before the individual
output channel is shut down. A user programmable retry limit allows the user to select how many times (1 to 40) the PIM will attempt to reconnect an output that was shut
down for an over-current condition. The PIM also provides redundant power supply capability (N+1) for multiple power supply configurations.